Part Number Hot Search : 
2E103K SNC203S MA142 A110L 74LS7 PLR15505 25001 AS4C4
Product Description
Full Text Search
 

To Download 8670 Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
  1description axioline ? f digital input and output module, 8 ? inputs, 24 ? v ? dc, 8 ? outputs, 24 ? v ? dc, 500 ? ma, single-conduc- tor connection technology axl f di8/1 do8/1 1h ? phoenix contact data sheet the module is designed fo r use within an axioline ? f station. it is used to acquire and output digital signals. the filter times of the inputs ca n be set to increase noise im- munity. filter times of 100 ? s allow the user to implement a counter function with a maximum input frequency of 5 ? khz in the ap- plication. the outputs are short-circuit and overload-protected . input features ? 8 digital inputs according to en ? 61131-2 type ? 1 and type ? 3 ?24 ? v ? dc, 2.4 ? ma ? connection of sensors in 1-wire technology ? filter times can be set in three increments: < ? 100 ? s, 1000 ? s or 3000 ? s ? maximum input frequency: 5 ? khz output features ? 8 digital outputs ? 24 v dc, 500 ma ? connection of actuators in 1-wire technology features of axioline f ? minimum update time < ? 100 ? s ? device type label stored ? diagnostic and status indicators this data sheet is only valid in association with the um ? en ? axl ? f ? sys ? inst user manual. make sure you always use the latest documentation. it can be downloaded from the product at phoenixcontact.net/products . 8670_en_02 2014-04-30
axl f di8/1 do8/1 1h 8670_en_02 phoenix contact 2 2table of contents 1 description ................................................................................................................... ........... 1 2 table of contents ............................................................................................................. ........ 2 3 ordering data ................................................................................................................. ......... 3 4 technical data ................................................................................................................ ......... 3 5 maximum outputs power cons umption when inductive load s are switched off ........................ 6 6 internal circuit diagram ...................................................................................................... ...... 7 7 terminal point assignment..................................................................................................... .. 8 8 connection example............................................................................................................ .... 8 9 local status and diagnostic indicators ..................................................................................... 9 10 process data................................................................................................................. ......... 10 11 parameter, diagnostics and info rmation (pdi) ....................................................................... 10 12 standard objects ............................................................................................................. ...... 11 12.1 objects for identifica tion (device rating plate) ............................................................................ 11 12.2 object for multilingual capacity .............................................................................................. 12 12.3 diagnostics objects ............................................................................................................ 12 12.4 objects for process data management .................................................................................... 13 13 application objects .......................................................................................................... ...... 14 13.1 substitute value (ff8dhex: pd output substitute configuration) ................................................... 14 13.2 filter time (ff8fhex: input_filter) .......................................................................................... 14 14 device descriptions .......................................................................................................... ..... 14
axl f di8/1 do8/1 1h 8670_en_02 phoenix contact 3 description type order no. pcs. / pkt. axioline ? f digital input and output module, 8 ? inputs, 24 ? v ? dc, 8 ? outputs, 24 ? v ? dc, 500 ? ma, single-conductor connection technology (including bus base module and connectors) axl f di8/1 do8/1 1h 2701916 1 3ordering data accessories type order no. pcs. / pkt. axioline ? f bus base module for housing type h (replacement item) axl f bs h 2700992 5 axioline ? f connector set (for e.g., ? axl ? f ? do16/1 ? 1h) (replacement item) axl cns 2l-o/d/uo/e1 2700986 1 zack marker strip for axioline ? f (device labeling), in 2 x 20.3 mm pitch, un- printed, 25-section, for in dividual labeling with b-stift 0.8, x-pen, or cms-p1-plotter (marking) zb 20,3 axl unprinted 0829579 25 zack marker strip, flat, in 10 mm pitch, unprinted, 10-section, for individual labeling with m-pen 0,8, x-pen, or cms-p1-plotter (marking) zbf 10/5,8 axl unprinted 0829580 50 insert label, roll, white, unlabele d, can be labeled with: thermomark roll, thermomark x, thermomark s1.1, mounting type: snapped into marker carrier, lettering field: 35 x 28 mm (marking) emt (35x28)r 0801602 1 documentation type order no. pcs. / pkt. user manual, english, axioline ? f: system and installation um en axl f sys inst - - user manual, english, axioline f: dia gnostic registers, and error messages um en axl f sys diag - - dimensions (nominal sizes in mm) width 35 mm height 126.1 mm depth 54 mm note on dimensions the depth is valid when a th ? 35-7.5 din rail is used (according to en ? 60715). 4 technical data 35 54 122,4 126,1 general data color traffic grey a ral 7042 weight 133 g ? (with connectors and bus base module) ambient temperature (operation) -25 c ... 60 c ambient temperature (storage/transport) -40 c ... 85 c permissible humidity (operation ) 5 % ... 95 % (non-condensing) permissible humidity (storage/transport) 5 % ... 95 % (non-condensing)
axl f di8/1 do8/1 1h 8670_en_02 phoenix contact 4 air pressure (operation) 70 kpa ... 106 kpa (up to 3000 m above sea level) air pressure (storage/transport) 70 kpa ... 106 kpa (up to 3000 m above sea level) degree of protection ip20 protection class iii, iec 61140, en 61140, vde 0140-1 mounting position any (no temperature derating) general data connection data designation axioline ? f connector connection method push-in technology conductor cross section solid / stranded 0.2 mm2 ? ... ? 1.5 mm2 ? / ? 0.2 mm2 ? ... ? 1.5 mm2 conductor cross section [awg] 24 ? ... ? 16 interface axioline ? f ? local bus connection method bus base module transmission speed 100 mbit/s communications power communications power u bus 5 v dc (via bus base module) current consumption from u bus max. 120 ma power consumption at u bus max. 600 mw i/o supply digital input and output module supply u io 24 v dc maximum permissible voltage range 19.2 v dc ... 30 v dc (including all tolerances, including ripple) current consumption from u io 8 a (external fuse) power consumption at u io typ. 440 mw (without actuators), max. 97.35 w (of which 1.35 ? w internal losses) surge protection of the supply voltage electronic (35 v, 0.5 s) polarity reversal protection of the supply voltage parallel diode; with external 5 ? a fuse (for startup only) protection max. 8 a (polarity re versal protection up to 5 ? a) when using for the first time, protect the module with a 5 a fuse . if all the modules are correctly connected in the system, t he 5 a fuse can be replaced by an 8 a fuse. you can now load the module up to 8 ? a. loads over 8 ? a are not permitted. note: damage to the electronics provide the module with an external fuse to protect it against polarity reversal. the power supp ly unit must be able to supply four times the nominal current of the external fuse, to ensu re that it trips in the event of an error. digital inputs number of inputs 8 connection method push-in technology connection method 1-wire description of the input en 61131-2 types 1 and 3 nominal input voltage 24 v dc nominal input current 2.4 ma current flow linear until nominal current is reached, then constantly approx. 2.4 ? ma input voltage range "0" signal -3 v dc ... 5 v dc input voltage range "1" signal 11 v dc ... 30 v dc input filter time 3000 s (default), 1000 s, < 100 s process data update < 100 s (bus-synchronous) polarity reversal protection of the inputs parallel diode (30 ? v, 5 ? s)
axl f di8/1 do8/1 1h 8670_en_02 phoenix contact 5 digital outputs number of outputs 8 connection method push-in technology connection method 1-wire nominal output voltage 24 v dc maximum output current per channel 500 ma maximum output current per device 4 a (external fuse) nominal load, ohmic max. 12 w (48 ? ; with nominal voltage) nominal load, inductive max. 12 va (1.2 h; 48 ? ; with nominal voltage) nominal load, lamp max. 12 w (at nominal voltage) signal delay max. 100 s (when switched on) signal delay max. 100 s (when switched off; with at least 50 ma load current) switching frequency max. 10000 per second (with at least 50 ? ma load current) switching frequency max. 1 per second (with inductive load) switching frequency max. 16 per second (with nominal lamp load) load min. 10 k ? energy consumption see diagram limitation of the voltage induced on circuit interruption -25.8 v ... -15 v output voltage when switched off max. 1 v output current when switched off max. 300 a behavior with overload shutdown with automatic restart behavior with inductive overload output can be destroyed reverse voltage resistance to short pulses limited protection up to 0.5 a for 1 s note: damage to the electronics if there is a faulty external voltage (rever se voltage) at one of the ou tputs, the output may be de stroyed. this may cause unin tentional setting of further outputs. overcurrent shut-down as of 0.7 a output current with ground connectio n interrupt when switched off < 1 ma short-circuit protection, overlo ad protection of the outputs electronic fieldbus data telegram fieldbus system profibus dp required parameter data 3 byte need for configuration data 7 byte error messages to the higher le vel control or computer system i/o supply failure yes short-circuit / overload of the digital outputs yes electrical isolation/isolation of the voltage areas test section test voltage 5 v communications power (logic), 24 v supply (i/o) 500 v ac, 50 hz, 1 min 5 v supply (logic)/functional earth ground 500 v ac, 50 hz, 1 min 24 v supply (i/o) / functional earth ground 500 v ac, 50 hz, 1 min mechanical tests vibration resistance in acc. with en ? 60068-2-6/iec ? 60068-2-6 5 g shock in acc. with en ? 60068-2-27/iec ? 60068-2-27 30 g continuous shock according to en ? 60068-2-27/iec ? 60068-2-27 10 g
axl f di8/1 do8/1 1h 8670_en_02 phoenix contact 6 5maximum outputs power consumption when inductive loads are switched off figure 1 maximum outputs power consumption when inductive loads are switched off the specifications in the diagram refer to a maximum switching frequency of 1 ? hz. the diagram shows the maximu m amount of energy that may be fed back into the corresponding output groups (out- puts 1 to 4, 5 to 8) for ea ch switch-off procedure when switching off an inductive load without external freewheeling circuit. the current data refers to th e ohmic dc voltage component of the inductive load. conformance with emc directive 2004/108/ec noise immunity test in accordance with en 61000-6-2 electrostatic discharge (esd) en ? 61000 - 4 - 2/iec ? 61000 - 4 - 2 criterion b; 6 kv contact discharge, 8 kv air discharge electromagnetic fields en ? 61000 - 4 - 3/iec ? 61000 - 4 - 3 criterion a; field intensity: 10 v/m fast transients (burst) en ? 61000 - 4 - 4/iec ? 61000 - 4 - 4 criterion b, 2 ? kv transient surge voltage (surge) en ? 61000 - 4 - 5/iec ? 61000 - 4 - 5 criterion b; dc supply lines: 0.5 kv/0.5 kv (symmetrical/asymmetrical) conducted interference en ? 61000 - 4 - 6/iec ? 61000 - 4 - 6 criterion a; test voltage 10 v noise emission test according to en 61000-6-3 radio interference properties en 55022 class b approvals for the latest approvals, please visit phoenixcontact.net/products. note: damage to the electronics restrict freewheeling voltage to a maximum of -17 ? v when using an external freewheeling circuit! the external freewheeling circuit does not function in the case of higher negative voltages. 0, 1 0, 2 0, 5 0, 6 0,7 0,8 0,9 1 ,0 1 , 11 , 21 , 31 , 41 , 51 , 61 ,7 1 ,8 1 ,9 2 ,0 2 , 12 , 22 , 32 , 4 0, 3 0, 4 0 0,0 5 0, 1 0, 15 0, 2 0, 25 0, 3 0, 35 0, 4 0 1 2 3 4 5 1 = 0,5 a 2 = 0,4 a 3 = 0,3 a 4 = 0,2 a 5 = 0,1 a inductance [h] energy consumption [j] only with external free running circuit
axl f di8/1 do8/1 1h 8670_en_02 phoenix contact 7 6 internal circuit diagram figure 2 internal wiring of the terminal points key: c d ui di 1... 8 u 24 v io u bus local bus input circuit 0 1 3 0 31 00 00 3 0 0 1 31 00 1 0 2 0 3 0 0 1 11 21 31 do 1... 8 0 3 13 23 33 0 2 12 22 32 output circuit 32 0 3 0 2 33 0 3 0 2 32 33 8x local bus axioline ? f local bus (hereinafter referred to as local bus) microcontroller transistor optocoupler led power supply unit electrically isolated areas input circuit input circuit output circuit output configuration c
axl f di8/1 do8/1 1h 8670_en_02 phoenix contact 8 7 terminal point assignment figure 3 terminal point assignment 8 connection example figure 4 typical connection of sensors and actuators when using external busbars ensure that gnd of the sens ors and actuators and gnd for u io have the same potential. termi- nal point color assignment supply voltage input a1, a2 red 24 v dc (u io ) supply to digital input and output modules (in- ternally jumpered) b1, b2 blue gnd reference potential of the supply voltage (in- ternally jumpered) digital inputs 00, 01, 10, 11 orange in1 ... in4 digital inputs 1 ... 4 20, 21, 30, 31 orange in5 ... in8 digital inputs 5 ... 8 digital outputs 02, 03, 12, 13 orange out1 ... out4 digital outputs 1 ... 4 22, 23, 32, 33 orange out5 ... out8 digital outputs 5 ... 8 0 3 00 13 1 0 23 2 0 33 3 0 a1 a2 b 1 b 2 00 10 20 30 01 11 21 31 02 12 22 32 03 13 23 33 a1 a2 b1 b2 + 2 4 v in7 + 2 4 v in 1 + 2 4 v 00 10 20 30 01 11 21 31 02 12 22 32 03 13 23 33 o ut8 o ut 2
axl f di8/1 do8/1 1h 8670_en_02 phoenix contact 9 9 local status and diagnostic indicators figure 5 local status and diagnostic indicators d ui o e 1 30 32 31 33 20 22 21 23 10 12 11 13 00 02 01 03 designation color meaning state description dred/ yellow/ green diagnostics of local bus communication power down off device in (power) reset. not con- nected red flash- ing device operating, but there is no connection to previous device. reset red on application reset device operating, but there is still a connection to the previous device, the application is reset. ready yellow on device operating, there is st ill a connection to the previous device, but the device has not yet detected a valid cycle after power on. connected yellow flashing valid data cycles have b een detected, but the device is (not) yet part of the current configuration. device ap- plication not active green/yel- low alter- nating valid data cycles are being detected. the master application set the output data to valid, however, the slave application has not set the input data to valid as yet. the master application set the output data to valid, however, the slave application cannot set the output data to valid as yet. active green flashing the device functions, communication within the station is ok. the input data is not being re ad by the master application. the master application has not yet set the output data to valid. (for example, the connection to th e controller is not yet established.) run green on valid data cycles are being detected. all data is valid uio green u input/output on supply for digital input and output modules is available. off supply for digital input and ou tput modules is not available. e1 red peripheral fault on short-circuit/overload of an output. off no i/o error 00, 01, 10, 11, 20, 21, 30, 31 yellow status of the inputs on input is set. off input is not set. 02, 03, 12, 13, 22, 23, 32, 33 yellow status of the outputs yellow on output is set. off output is not set. for more information on the meaning of local diagnostic and status in dicators, please refer to the um ? en ? axl ? f ? sys ? inst user manual.
axl f di8/1 do8/1 1h 8670_en_02 phoenix contact 10 10 process data the i/o data is displayed in s7-compatible format. 11 parameter, diagnostics and information (pdi) parameter and diagnost ic data as well as other information is transmitted via the pdi channel of the axioline ? f station. the standard and application ob jects stored in the module are described in the following section. the following applies to all tables below: please refer to the um ? en ? axl ? f ? sys ? inst for an explana- tion of the object codes and data types. input process data byte 0 bit 76543210 channel87654321 terminal point 31 30 21 20 11 10 01 00 output process data byte 0 bit 76543210 channel87654321 terminal point 33 32 23 22 13 12 03 02 abbreviation meaning a number of elements l length of the elements rread wwrite every visible string is terminated with a zero terminator (00 hex ). the length of a visible string element is therefore one byte larger than the amount of user data. for detailed informatio n on pdi and the ob- jects, please refer to the um ? en ? axl ? f ? sys ? inst user manual.
axl f di8/1 do8/1 1h 8670_en_02 phoenix contact 11 12 standard objects 12.1 objects for identificati on (device rating plate) index (hex) object name object type data type a l rights meaning contents manufacturer 0001 vendorname var visible string 1 16 r manufacturer name phoenix contact 0002 vendorid var visible string 1 7 r manufacturer identifi- cation 00a045 0003 vendortext var visible st ring 1 49 r comment on the manufacturer components and systems for indus- trial automation 0012 vendorurl var visible string 1 30 r url of the manufac- turer http://www.phoenix- contact.com module - general 0004 devicefamily var visible string 1 1 9 r device family i/o digital in-out 0006 productfamily var visible string 1 33 r product family axioline - high speed i/o system 000e commprofile var visible string 1 4 r communication pro- file 633 000f deviceprofile var visible string 1 5 r device profile 0010 0011 profileversion record visible string 2 11; 20 r device profile version 2011-12-07; basic profile v2.0 003a versioncount array unsigned 16 4 4 * 2 r version counter e.g., 0007 0001 0000 0000 module - special 0005 capabilities array visible string 1 8 r properties nothing 0007 productname var visible string 1 21 r pr oduct designation axl f di8/1 do8/1 1h 0008 serialno var visible string 1 11 r serial number xxxxxxxxxx (e. ? g., 1234512345) 0009 producttext var visible string 1 55 r product text 8 digital inputs, ad- justable filter, 8 ? digi- tal ? outputs 000a ordernumber var visible string 1 8 r order no. 2701916 000b hardwareversion record visible string 2 11; 3 r hardware version e. ? g., 2011-02-04; 00 000c firmwareversion record visible string 2 11; 3 r firmware version 0000-00-00; -- 000d pchversion record visible string 2 11; 6 r parameter channel version 2010-01-08; v1.00 0037 devicetype var octet string 1 8 r module identification 00 c0 00 01 00 00 00 dd hex use of the device 0014 location var visible string 1 59 r/w insta llation location can be filled out by the user. 0015 equipmentident var visible string 1 59 r/w eq uipment identifier can be filled out by the user. 0016 appldeviceaddr var unsigned 16 1 2 r/w user-defined device number can be filled out by the user.
axl f di8/1 do8/1 1h 8670_en_02 phoenix contact 12 12.2 object for multilingual capacity 12.3 diagnostics objects diagnostics state (0018 hex : diagstate) this object is used for a structured message of an error. error code and status of the local status and diagnostics indicators index (hex) object name object type data type a l rights meaning contents 0017 language record visible string 2 6; 8 r language en-us; english index (hex) object name object type data type a l rights assignment/content 0018 diagstate record ? 6 2; 1; 1; 2; 1; 1 r diagnostics state; see below 0018 hex : diagstate (read) subindex data type length in bytes meaning contents 0 record 8 diagnostic state complete diagnostics information 1 unsigned 16 2 error number 0 ... 65535 dec 2 unsigned 8 1 priority 00 hex no error 01 hex error 02 hex warning 81 hex error removed 82 hex warning eliminated 3unsigned 81 group 00 hex no error ff hex entire device 4 unsigned 16 2 error code see table below 5 unsigned 8 1 more information fol- lows 00 hex (not supported) 6 visible string 1 text 00 hex (not supported) the message with the priority 81 hex or 82 hex is a one-time internal message to the bus cou- pler that is implemented onto the error mech- anisms of the higher-level system by the bus coupler. after all errors have been eliminated, it is au- tomatically reset. error code error priority group d led uio led e1 led 0000 hex no error 00 hex 00 hex green on on off 3400 hex i/o supply failure 01 hex ff hex flashing green/yellow off off 2344 hex short-circuit/overload of an output. 02 hex ff hex green on on red on
axl f di8/1 do8/1 1h 8670_en_02 phoenix contact 13 12.4 objects for process data management the objects 003b hex and 003c hex are only applicable to tools. in process data (0025 hex : pdin) you can read the in process data of the module with this object. the structure corresponds to the repres entation in the "process data" section. out process data (0026 hex : pdout) you can write the output process data of the module with this object. the structure corresponds to the repres entation in the "process data" section. index (hex) object name object type data type a l rights assignment 0025 pdin var octet string 1 1 r input process data 0026 pdout var octet string 1 1 r output process data 003b pdin_descr array of records ? 3 8; 2; 2 r description of the in process data 003c pdout_descr array of records ? 3 8; 2; 2 r description of the output pro- cess data 0025 hex : pdin (read) subindex data type length in bytes meaning 0 octet string 1 input process data 0026 hex : pdout (read) subindex data type length in bytes meaning 0 octet string 1 output process data
axl f di8/1 do8/1 1h 8670_en_02 14 phoenix contact gmbh & co. kg ? 32823 blomberg ? germany phoenixcontact.com 13 application objects 13.1 substitute value (ff8d hex : pd output substitute configuration) configure the substitute value with whic h the module is to be operated with an application reset using this object. 13.2 filter time (ff8f hex : input_filter) configure the filter time of the module using this object. 14 device descriptions the device is described in the device description files. the device descriptions for controllers from phoenix con- tact are included in pc worx and the corresponding service packs. the device description files for other systems are available for download at phoenixcontact.net/products in the down- load area of the bus coupler used. index (hex) object name object type data type a l rights assignment ff8d pd output substi- tute configuration var unsigned 8 1 1 r/w substitute value ff8f input_filter var unsigned 8 1 1 r/w filter time ff8d hex : pd output substitute co nfiguration (read, write) subindex data type length in bytes contents 0var100 hex (default) "0" output to all output bits 01 hex hold last value ff8f hex : input_filter (read, write) subindex data type length in bytes contents 0var100 hex (default) 3000 ? s 01 hex 1000 s 02 hex < 100 s


▲Up To Search▲   

 
Price & Availability of 8670

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X